Fibre optics

Fibre optics, from light to link

Fibre carries almost every link I design beyond the desk: between floors, between racks and between sites. This page explains how light travels in single mode and multimode fibre. It then covers fibre grades, reach, cables, connectors, polarity, transceivers, splicing, loss budgets, testing and safety, and ends with a fault finder.

  • Single mode and multimode
  • OM and OS grades
  • Reach
  • LC and MPO
  • Polarity
  • SFP to OSFP
  • Loss budgets
  • OTDR and inspection
  • PON
Light travelling both ways over a fibre pair between two switches Two switches, each with an optic, are joined by a pair of fibres. Pulses of light travel from left to right on one fibre and from right to left on the other. In the middle, a cross section shows the 9 micron core inside the 125 micron cladding. transmit receive 125 µm cladding 9 µm core SwitchSFP28 optic SwitchSFP28 optic
Live view · light both ways on a fibre pair
How fibre works

Light in glass, and why it reaches so far

Fibre carries data as pulses of light, usually infrared, through a glass core thinner than a hair. Everything else on this page, from fibre types to loss budgets, follows from two ideas: how many paths the light can take, and how much of it is lost on the way.

Light in multimode and single mode fibre Two fibres side by side. In the multimode fibre, light takes several paths through the wide 50 micron core: one straight down the middle and others that bounce off the edge of the core. The longer paths arrive later, so a short pulse spreads out by the far end. In the single mode fibre the 9 micron core carries one path, so the pulse arrives still sharp. Multimode · 50 µm core cladding core Single mode · 9 µm core cladding core Pulse at the far end spread out still sharp Not to scale. Both fibres are 125 µm across the cladding.

Swipe sideways to see the whole diagram.

Animation

Orange packets take different paths through the multimode core and arrive at different times. That spread, called modal dispersion, is what limits multimode reach. The teal packets in single mode share one path, which is why single mode reaches tens of kilometres.

Core and cladding

A fibre is a glass core inside a glass cladding with a slightly lower refractive index, 125 µm across in total. A plastic coating takes it to 250 µm, or 200 µm for some newer fibres.

Total internal reflection

Light that meets the cladding at a shallow enough angle reflects back into the core every time, so it follows the fibre round gentle bends. A tight bend lets light escape. That loss is a macrobend.

Modes

A mode is one path light can take. A 50 µm or 62.5 µm core carries many modes, so it is multimode. A 9 µm core carries one, so it is single mode.

Dispersion

A pulse spreads as it travels. In multimode fibre most of the spread comes from modes arriving at different times. In single mode, colours travelling at slightly different speeds cause it (chromatic dispersion).

Attenuation

Glass absorbs and scatters a little light per km. It is measured in dB (decibels): 3 dB is half the light, and 10 dB is a tenth. Connectors and splices add more.

Why fibre

Fibre carries more bandwidth over longer distances than copper, ignores electrical noise and lightning, and needs no earthing between buildings. It is also light and thin, which matters in a full tray.

The wavelengths in use

The wavelength windows fibre uses A chart of fibre attenuation against wavelength from 800 to 1650 nanometres. Single mode loss falls from about 2 dB per km near 800 nm to about 0.35 at 1310 nm and 0.2 at 1550 nm. Multimode is marked at 850 nm at about 2.5 dB per km and at 1300 nm. Shaded bands mark the 850 nm multimode window, the OM5 shortwave band, the O band, the water peak, the PON downstream band and the C band. 1 2 3 850 nm 1000 nm 1310 nm 1550 nm Attenuation, dB per km (typical) old water peak multimode single mode Multimode: about 2.5 dB/km OM5 band: 850 to 953 nm O band: about 0.35 dB/km Low water peak fibre: G.652.D C band: about 0.2 dB/km GPON 1490 down, 1310 up

Swipe sideways to see the whole diagram.

850 nm. The multimode window. Cheap VCSEL (vertical cavity surface emitting laser) optics work here, and almost every short reach data centre link uses it. Loss is high, about 2.5 dB per km in practice, but the links are short.

850 to 953 nm. OM5 fibre is specified across this band, so shortwave WDM (wavelength division multiplexing) and BiDi (bidirectional) optics can put two or four wavelengths on each fibre.

1310 nm, the O band. Standard single mode fibre has almost no chromatic dispersion here, so LR (long reach) optics and most data centre single mode optics use it. Loss is about 0.35 dB per km.

The water peak, 1383 nm. Older fibre lost a lot of light here because of water in the glass. Low water peak fibre (ITU-T G.652.D) removed most of it, which opened the whole band for CWDM (coarse WDM) from 1271 to 1611 nm.

1550 nm, the C band. The lowest loss, about 0.2 dB per km, and the band optical amplifiers work in. Long haul links, DWDM (dense WDM) and coherent long reach optics live here.

PON (passive optical network) wavelengths. GPON sends downstream at 1490 nm and upstream at 1310 nm. XGS-PON uses 1577 nm down and 1270 nm up, so both can share one fibre.

Animation
WavelengthFibreWhat uses itLoss
850 nmMultimodeVCSEL lasers, the cheapest opticsAbout 2.5 dB/km in practice; 3.5 dB/km is the long standing TIA (Telecommunications Industry Association) maximum
1300 nmMultimodeThe older LED (light emitting diode) windowAbout 0.6 dB/km; 1.5 dB/km maximum
1310 nmSingle mode (O band)Low dispersion: most data centre single mode opticsAbout 0.35 dB/km (typical)
1490 and 1577 nmSingle modePON downstream (GPON, XGS-PON)About 0.2 to 0.25 dB/km (typical)
1550 nmSingle mode (C band)Lowest loss; long reach and DWDMAbout 0.2 dB/km (typical)

Loss figures marked typical are what good modern fibre measures. The maximums are the values cabling standards allow, which I use for worst case design. Copper links and the 100 m rule are on the copper cabling page.

Fibre types

OM1 to OS2, and what each one is for

Multimode fibre is graded OM1 to OM5 by its modal bandwidth: how well it keeps a laser pulse together. Single mode is graded by loss. The grade, more than anything else, sets how far a link can reach.

Fibre types side by side A cross section of a fibre on the left shows the 125 micron cladding and the 250 micron coating. The core is drawn to scale for each type: 62.5 microns for OM1, 50 microns for OM2 to OM5, and 9 microns for OS2. On the right, a length of cable in the standard jacket colour for the chosen type, with its modal bandwidth and typical use. 62.5 µm core 50 µm core 50 µm core 50 µm core 50 µm core 9 µm core 125 µm cladding 250 µm coating OM1 · Orange jacket Modal bandwidth200 MHz·km at 850 nmBest used forLegacy campus links at 1 Gb/s. I replace it ratherthan extend it. OM2 · Orange jacket Modal bandwidth500 MHz·km at 850 nmBest used forLegacy 1 Gb/s links, and short 10 Gb/s runs. OM3 · Aqua jacket Modal bandwidth2000 MHz·km at 850 nmBest used forLaser optimised for VCSELs: 10G to 100G short reach. OM4 · Aqua jacket Modal bandwidth4700 MHz·km at 850 nmBest used forMy default multimode for data centres: 10G to 400G. OM5 · Lime green jacket Modal bandwidth4700 at 850 nm and 2470 at 953 nmBest used forWideband: several wavelengths per fibre for SWDM andBiDi optics. OS2 · Yellow jacket Modal bandwidthNot limited by modesBest used forBetween buildings and sites, and most new linksabove 100G.

Swipe sideways to see the whole diagram.

OM1. A 62.5 µm core from the LED era. It cannot be joined to 50 µm fibre without a large loss, and 10G reaches only 33 m. Where I find it, I plan to replace it.

OM2. The first 50 µm grade. It still carries 1G for 550 m, but its low modal bandwidth limits 10G to 82 m.

OM3. Laser optimised 50 µm fibre, made for the VCSEL lasers in short reach optics. It carries 10G for 300 m and 100G for 70 m.

OM4. A higher modal bandwidth version of OM3, with more reach at every speed: 400 m at 10G and 100 m at 100G. Most jackets are aqua, and some makers in Europe use violet.

OM5. Specified from 850 to 953 nm, so BiDi and shortwave WDM optics can run several wavelengths per fibre. At a single 850 nm wavelength it behaves like OM4.

OS2. Single mode fibre with a maximum loss of 0.4 dB per km. Reach is set by the optics, from 500 m to 80 km and beyond. Jackets are yellow.

Animation
TypeCoreModal bandwidth or lossJacket (TIA-598)Where it fits
OM162.5 µm200 MHz·kmOrangeLegacy only
OM250 µm500 MHz·kmOrangeLegacy 1G
OM350 µm2000 MHz·kmAqua10G to 400G short reach
OM450 µm4700 MHz·kmAqua (violet from some makers)10G to 400G short reach, longer
OM550 µm4700 at 850 nm, 2470 at 953 nmLime greenSeveral wavelengths per fibre
OS1a9 µmNot mode limited; 1.0 dB/km maximumYellowIndoor single mode
OS29 µmNot mode limited; 0.4 dB/km maximumYellowIndoor, outdoor and long distance

How I choose

For new work I fit OS2 for anything between buildings, between floors over about 100 m, and for most new links above 100G. Inside a data centre row, OM4 still gives the cheapest short reach optics.

OM classes and OS classes

ISO/IEC 11801 defines the OM (optical multimode) and OS (optical single mode) classes. OS1a, from the 2017 edition, is the indoor single mode class at 1.0 dB per km, and OS2 is the low loss class at 0.4 dB per km.

Bend insensitive fibre

ITU-T G.657 fibre tolerates tighter bends than standard G.652.D. A G.657.A1 fibre is rated down to 10 mm radius, A2 to 7.5 mm and B3 to 5 mm, which suits tight trunking and home installs.

The print beats the colour

Jacket colours are a convention, not a guarantee. TIA allows other colours when the jacket print states the fibre type, so I read the print and the drawings before I patch.

Reach

How far each optic goes on each fibre

Every optic is specified for a reach on each fibre grade. Faster multimode optics reach less, because the pulses are shorter and spread matters more. Single mode reach is set by the optic, from 500 m to tens of kilometres.

OpticOM1OM2OM3OM4OM5OS2
1000BASE-SX275 m550 m1000 m*1000 m*1000 m*No
1000BASE-LXNoNoNoNoNo5 km
10GBASE-SR33 m82 m300 m400 m400 mNo
10GBASE-LRNoNoNoNoNo10 km
25GBASE-SRNoNo70 m100 m100 mNo
40GBASE-SR4NoNo100 m150 m150 mNo
40G BiDiNoNo100 m150 m200 mNo
100GBASE-SR4NoNo70 m100 m100 mNo
100G BiDi or SWDM4NoNo70 m100 m150 mNo
100GBASE-DRNoNoNoNoNo500 m
100GBASE-FR1NoNoNoNoNo2 km
100GBASE-LR4NoNoNoNoNo10 km
400GBASE-SR8NoNo70 m100 m100 mNo
400GBASE-SR4.2NoNo70 m100 m150 mNo
400GBASE-DR4NoNoNoNoNo500 m
400GBASE-FR4NoNoNoNoNo2 km
400GBASE-LR4-6NoNoNoNoNo6 km

Reach is the IEEE 802.3 or MSA (multi source agreement) figure for the standard optic. * 1000BASE-SX on OM3 and above: the standard specifies OM1 and OM2 only, and vendors quote about 1 km. Extended reach optics from vendors go further, at a price. 1000BASE-LX is specified to 5 km, and many 1000BASE-LX optics are rated to 10 km.

Try it: will this link reach?

Fits. 10GBASE-SR on OM4 is specified to 400 m, so a 250 m link has 150 m to spare. Check the loss budget too: reach assumes the standard allowance for connectors.

Standard reach
400 m
Your link
250 m
Headroom
150 m
Cables

What is inside a fibre cable

The fibre is the same in every cable. What changes is how it is protected: from pulling, temperature, water, crushing and fire. The construction decides where a cable can go and how fast it can be terminated.

Inside fibre cables Cross sections of four fibre cables. Tight buffered: six fibres, each in a thick buffer, inside aramid yarn and a jacket. Loose tube: six coloured tubes, each holding four fibres, around a central strength member. Ribbon: four ribbons of twelve fibres in a central tube. Armoured: loose tubes inside a corrugated steel layer and an outer sheath. Tight bufferedEach fibre has its own 900 µm buffer, so it can beterminated or spliced straight away. Aramid yarntakes the pulling load. Used indoors: risers,patch cords and short building runs. Loose tubeFibres float in gel filled or dry tubes, so the cablecan stretch and change temperature without strainon the glass. A central strength member resistspulling. Used outdoors, in ducts and between buildings. RibbonTwelve fibres bonded side by side in each ribbon,so one mass fusion splice joins twelve at once.Used for high fibre counts: 144 fibres and more,and for MPO trunks. ArmouredA corrugated steel tape under an outer sheathprotects against crushing and rodents. Used fordirect burial and exposed routes. The steelmust be earthed where the cable enters a building. Cross sections, not to scale

Swipe sideways to see the whole diagram.

Tight buffered. Easy to work with and to terminate, but the glass shares the strain when the cable is pulled or gets cold. I use it inside buildings.

Loose tube. The tubes protect the fibres from strain and temperature. Each tube and each fibre follows the colour code, so tube 2, fibre 3 is orange tube, green fibre.

Ribbon. The densest construction. Mass fusion splicing joins a whole ribbon in one go, which saves days on a large build.

Armoured. Heavier and stiffer, with a larger bend radius. The metal armour needs earthing and bonding where it enters a building.

Animation
ConstructionWhat it isWhere I use it
Tight buffered900 µm buffer on each fibreInside buildings, risers, patch cords
Loose tubeFibres in gel filled or dry tubesOutdoors, ducts, between buildings
Ribbon12 fibres bonded side by sideHigh fibre counts and MPO (multi fibre push on) trunks
ArmouredSteel tape or corrugated steelDirect burial and rodent risk
Blown fibreFibre units blown into microducts laterCampuses that will grow

The fibre colour code

  • 1 Blue
  • 2 Orange
  • 3 Green
  • 4 Brown
  • 5 Slate
  • 6 White
  • 7 Red
  • 8 Black
  • 9 Yellow
  • 10 Violet
  • 11 Rose
  • 12 Aqua

TIA-598 sets the order for fibres in a tube and for tubes in a cable. After twelve, the sequence repeats with a stripe or ring mark. I record tube and fibre numbers on every splice and patch schedule, never just a colour.

Indoor fire performance

Indoor cable in the UK and EU is rated under the CPR (Construction Products Regulation). LSZH (low smoke zero halogen) sheaths give off less smoke and no acid gas. The ratings are on the copper cabling page.

Outdoor cable indoors

Outdoor polyethylene sheaths are not made for long indoor runs. I change to an indoor or universal cable at a joint near the building entry, as the fire strategy requires.

Bend radius

I keep to the maker's bend radius: typically 10 times the cable diameter when it is not under load, and 20 times while it is being pulled. Bend insensitive fibre helps, but the cable still has limits.

Fibre counts

Cables come in 12, 24, 48, 96, 144 fibres and more. I size for today's need plus spare fibres, because pulling a second cable later costs far more than the extra fibres.

Connectors

LC, SC, MPO and the rest, and how they meet

A connector holds the fibre in a ceramic ferrule and presses two ferrules end to end, so the cores line up within a micron or so. Most losses and most faults in a fibre link happen at connectors. The LC (Lucent connector) is the one I handle most.

Fibre connectors and end faces A row of seven connector types: LC, SC, ST, FC, MPO, the very small form factor SN and MDC, and the UPC and APC end faces. Choosing one shows a larger drawing of it with its ferrule size, how it latches, where it is used and a caution. The end face view shows light reflecting straight back from a UPC face, and away from the core on an angled APC face. LC SC ST FC MPO SN and MDC UPC and APC LC (Lucent connector)1.25 mm ferrule, push and latchAlmost every SFP and QSFP duplex portUsually used as a duplex pair with a clip SC (subscriber connector)2.5 mm ferrule, square push pull bodyOlder panels, PON and FTTP (fibre to the premises)Often green bodied APC in service provider work ST (straight tip)2.5 mm ferrule, bayonet twist lockLegacy multimode and industrial sitesEasy to under insert, so I check each one FC (ferrule connector)2.5 mm ferrule, threaded nutTest equipment and older single modeHolds well where there is vibration MPO (multi fibre push on)12, 16 or 24 fibres per row in one ferruleParallel optics (SR4, DR4, SR8) and trunksMale has pins, female has holes; MTP is a brand SN and MDC (very small form factor)Two 1.25 mm ferrules stacked vertically400G and 800G breakout ports, dense panelsAbout three times LC density; they do not mate UPC reflects backAPC angles it awayUPC and APC end facesUPC: domed flat end, about 50 dB return lossAPC: 8 degree angle, about 60 dB or moreNever mate UPC with APC: high loss and damage

Swipe sideways to see the whole diagram.

LC. The small form factor connector on almost every pluggable optic. A duplex LC carries transmit and receive, and the clip often lets me swap the pair if the polarity is wrong.

SC. Larger and easy to handle. Still common in older patch panels, and in fibre to the premises, where the APC (angled physical contact) version is the norm.

ST. A bayonet connector from older multimode networks. I still meet it on plant floors and in older riser panels.

FC. A threaded connector that holds firm under vibration. Mostly on test gear and older single mode equipment now.

MPO. Many fibres in one rectangular ferrule, for parallel optics and for trunks that break out to LC. Pinned and unpinned ends must pair correctly, and the key sets polarity.

SN and MDC. VSFF (very small form factor) connectors put a duplex pair in a body about a third the width of a duplex LC. Several fit in one QSFP-DD port, so a 400G optic can break out without a cassette.

UPC and APC. UPC (ultra physical contact) end faces reflect a little light straight back. APC end faces are angled at 8 degrees, so the reflection leaves the core. APC is green; UPC single mode is blue.

Animation
ConnectorFerruleCouplingWhere I see it
LC (Lucent connector)1.25 mmPush and latchMost duplex pluggable optics, patch panels
SC (subscriber connector)2.5 mmPush pullOlder panels, PON and FTTP (fibre to the premises)
ST (straight tip)2.5 mmBayonetLegacy multimode, industrial
FC (ferrule connector)2.5 mmThreadedTest equipment, older single mode
MPO and MTP12, 16 or 24 fibres per rowPush pull, pinned or unpinnedParallel optics and trunks
SN, MDC and CS1.25 mm, duplexPush pull400G and 800G breakout, very dense panels

Connector and adapter colours

ColourMeaning
BeigeMultimode 62.5 µm (OM1)
BlackMultimode 50 µm (OM2)
AquaMultimode OM3 and OM4
Lime greenMultimode OM5
BlueSingle mode UPC
GreenSingle mode APC

Return loss matters more on single mode

Light reflected back into a single mode laser upsets it, and reflections ruin analogue video and PON. That is why service provider and FTTP work uses APC, and why I never mix UPC and APC in one mated pair.

Pinned and unpinned MPO

Two MPO connectors only mate if one has guide pins and the other does not. Transceivers are usually pinned, so the patch cords to them are unpinned. I record pin state on every MPO schedule.

SN and MDC are not the same

Both put two 1.25 mm ferrules in a narrow body, and they look alike. They do not mate with each other, so I standardise on one per site.

Field or factory

Factory polished, pre terminated cables give the lowest loss and the fastest install. Field terminations, by splicing a factory made pigtail, suit cables whose length is not known in advance.

Polarity

Making sure transmit meets receive

Every fibre link sends on one fibre and receives on another. Polarity is the plan that makes sure each transmitter reaches the right receiver, through every cord, panel and trunk. Most "no light" faults on new installs are polarity.

Duplex polarity: transmit must meet receive Two switches joined by a patch cord, a permanent link between two patch panels, and a second patch cord. Each piece crosses the two fibres over. With three crossings, light from each transmit port reaches the receive port at the far end. In the last step one cord is straight, giving two crossings, so transmit meets transmit and the link fails. Switch A Switch B panel panel TxRx TxRx patch cord permanent link patch cord Two crossings: transmit meets transmit Three crossings: transmit meets receive

Swipe sideways to see the whole diagram.

Step 1
  1. Light leaves switch A on its transmit fibre and must arrive on switch B's receive fibre, and the same the other way. Every duplex link is two one way paths.

  2. In the TIA A to B scheme, a duplex patch cord connects position A at one end to position B at the other. So each cord crosses the pair once.

  3. The installed cabling between panels is also built A to B, so it crosses once more. Panels and adapters keep the order they are given.

  4. Cord, link, cord: three crossings, an odd number. Transmit lands on receive at both ends and the link comes up.

  5. Swap one cord for an A to A cord and there are two crossings. Transmit meets transmit, both receivers see no light, and the ports stay down.

Try it: does transmit meet receive?

The link comes up. Three crossings, an odd number, so transmit lands on receive at both ends.

Crossings
3
Switch A transmit lands on
Switch B receive

MPO trunks and polarity methods

MPO polarity methods A, B and C Twelve fibre positions at each end of an MPO trunk, in the standard colours. Type A runs straight through, position 1 to 1. Type B reverses, position 1 to 12. Type C swaps each pair, position 1 to 2 and 2 to 1. Each method also sets whether the far end key is up or down. 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12 End 1, key up End 2, key down End 2, key up End 2, key down Type A: straight, 1 to 1 Type B: reversed, 1 to 12 Type C: pairs flipped, 1 to 2

Swipe sideways to see the whole diagram.

Method A. A Type A trunk keeps the order: fibre 1 to fibre 1. One end is key up and the other key down. The pair is flipped by using an A to B cord at one end and an A to A cord at the other, so two kinds of cord are needed.

Method B. A Type B trunk reverses the order: fibre 1 to fibre 12. Both ends are key up, which suits parallel optics such as SR4 and DR4. A to B cords work at both ends. Key up to key up does not suit angled APC MPO connectors.

Method C. A Type C trunk flips each pair inside the cable, so A to B cords work at both ends for duplex links. It does not suit parallel optics, so I avoid it for new builds. TIA-568.3-E adds universal methods, U1 and U2, built on Type B trunks.

Animation

The rule I check

For a duplex path, count every crossing from one transceiver to the other. An odd number works. An even number puts transmit on transmit, and both ports stay dark.

Parallel optics

An SR4 or DR4 optic transmits on fibres 1 to 4 and receives on 9 to 12. A Type B path, key up at both ends, maps 1 to 12 and lands every transmit lane on a receive lane.

One method per site

Mixing methods is how polarity faults start. I set one method in the design, record it on every schedule, and order cassettes and cords to match.

Fix it at the cord

When a duplex link has the wrong polarity, I swap the pair at one patch cord, which many LC clips allow, rather than changing the panel. Then I update the record.

Transceivers

The optic at each end, from SFP to OSFP

A transceiver, or optic, turns the switch's electrical lanes into light and back. Its form factor sets the speed, its optical type sets the fibre and reach, and both ends must match.

Inside a pluggable optic A pluggable optic between a switch chip and the fibre. On the transmit side, electrical lanes from the switch pass a retimer or DSP (digital signal processor), a laser driver and a laser, then leave as light. On the receive side, light reaches a photodiode, an amplifier and a retimer, then returns to the switch as electrical lanes. A monitoring chip reports temperature, laser bias and optical power to the switch over a management bus. Pluggable optic Switch ASIChost lanes Retimeror DSP Laser driver LaserVCSEL or DFB DOMtemp, bias, power Retimeror DSP Amplifiertransimpedance Photodiode to the fibre from the fibre management bus One lane shown. Multi lane optics repeat the chain per lane or per wavelength.

Swipe sideways to see the whole diagram.

Animation

Orange packets are the transmit path from the switch ASIC (application specific integrated circuit), teal the receive path, and purple the DOM (digital optical monitoring) readings the switch polls. The retimer or DSP (digital signal processor) cleans up the electrical signal. Short reach optics use cheap VCSEL lasers at 850 nm; single mode optics use DFB (distributed feedback) or EML (electro absorption modulated) lasers.

Form factorElectrical lanesCommon speedsOptical connector
SFP (small form factor pluggable)1 lane1GDuplex LC
SFP+1 lane10GDuplex LC
SFP281 lane25GDuplex LC
SFP561 lane, PAM4 (four level pulse amplitude modulation)50GDuplex LC
QSFP+ (quad SFP)4 × 10G40GDuplex LC or MPO-12
QSFP284 × 25G100GDuplex LC or MPO-12
QSFP564 × 50G, PAM4200GDuplex LC or MPO-12
QSFP-DD (double density)8 × 50G or 8 × 100G, PAM4400G, 800GDuplex LC, MPO, SN or MDC
OSFP (octal SFP)8 × 50G or 8 × 100G, PAM4400G, 800GAs QSFP-DD; larger, with room for more cooling

PAM4 (four level pulse amplitude modulation) sends two bits per symbol, where NRZ (non return to zero) sends one. It doubles the data rate per lane, and it is why 50G and 100G lanes need forward error correction. DAC (direct attach copper), AOC (active optical cable) and breakout cables are on the data centre cabling page.

Reading the name of an optic

CodeMeaningWhat it tells me
SRShort reachMultimode at 850 nm: tens to hundreds of metres
DRData centre reachSingle mode, 500 m, often parallel (DR4 uses four fibre pairs)
FRFar reachSingle mode, 2 km, usually four wavelengths on one pair (FR4)
LRLong reachSingle mode, 10 km (400GBASE-LR4-6 is 6 km)
ERExtended reachSingle mode, 40 km
ZRThe 80 km classSingle mode, coherent optics for data centre interconnect
BiDiBidirectionalTwo wavelengths on each fibre, so 40G or 100G runs on one duplex pair
SWDM4, CWDM4Wavelength multiplexingFour wavelengths on one duplex pair: SWDM (shortwave WDM) on multimode, CWDM near 1310 nm on single mode

The number after the code counts lanes: four fibre pairs, or four wavelengths. A suffix such as .2 means two wavelengths per fibre, as in 400GBASE-SR4.2.

What the DOM tells me

ReadingWhat it measuresWhat I look for
TemperatureInside the moduleHigh values point to poor airflow or a failing module
Supply voltageFrom the hostRarely the problem, but worth a look
Laser bias currentDrive current to the laserRising over months means the laser is ageing
Transmit powerLight leaving the module, in dBmLow means a failing laser
Receive powerLight arriving, in dBmLow means loss on the path: dirt, bends or distance. Too high on short single mode runs can overload the receiver

Coding and compatibility

Switches read the module's EEPROM (electrically erasable memory) and some refuse optics they do not recognise. I buy optics coded for the platform, and check the vendor's compatibility matrix for the exact switch and software release.

Both ends must match

An SR optic only talks to an SR optic on the same fibre type. A 100GBASE-LR4 will not talk to a 100GBASE-FR1, even though both are single mode. I put the optic type on every link record.

Heat and power

A 400G or 800G optic can draw over 10 W (typical), so a switch full of them needs the airflow its design assumes. Blanking plates in empty ports matter.

Wavelength division

CWDM (coarse wavelength division multiplexing) spaces wavelengths 20 nm apart from 1271 to 1611 nm. DWDM (dense WDM) packs them much closer in the C band. Both put many links on one fibre pair.

Splicing

Joining fibre so the light barely notices

Fibre is joined by splicing, either fused into one piece of glass or held end to end in a sleeve. Splices join cable lengths, fit connectors in the field, and repair breaks.

A fusion splice, step by step Two coated fibres approach a pair of electrodes. The steps strip the coating, clean and cleave the bare glass, align the cores, fuse them with an electric arc, show the estimated loss, and slide a protective heat shrink sleeve over the joint. Strip the coating: about 30 mm Clean the bare glass with alcohol Cleave flat: under 1 degree Align the cores, often by camera Fuse with an electric arc Estimated loss: about 0.02 dB Protect with a heat shrink sleeve coated fibre coated fibre

Swipe sideways to see the whole diagram.

Step 1
  1. I strip the 250 µm coating from both ends, leaving bare 125 µm glass. A thermal or mechanical stripper keeps the glass unscratched.

  2. I wipe the bare glass with lint free tissue and pure alcohol, once and in one direction. Any dirt now ends up in the joint.

  3. A precision cleaver scores and snaps the glass to leave a flat, square end. A poor cleave angle is the main cause of a high loss splice.

  4. The splicer moves both fibres into line. Core alignment splicers use cameras to line up the cores themselves, which matters most on single mode.

  5. An electric arc melts the two ends together into one piece of glass. The whole fuse takes a few seconds.

  6. The splicer estimates the loss from its images. A good fusion splice is typically a few hundredths of a dB. I test the whole link afterwards, because the estimate is not a measurement.

  7. A heat shrink sleeve with a steel rod protects the joint. It goes into a splice tray, in order, with tube and fibre numbers recorded.

MethodHow it worksLossWhere I use it
Fusion spliceGlass melted into one pieceTypically under 0.05 dB (indicative)Joining cables, pigtails, repairs
Mechanical spliceEnds held in a gel filled sleeveA few tenths of a dB (indicative)Quick repairs and some field kits
Factory pre terminatedConnectors fitted and tested in the factoryLowest connector loss, with a test reportData centre trunks and known lengths
Spliced pigtailFactory connector on a short tail, spliced onFactory connector loss plus one spliceField termination of any cable

Mass fusion

Ribbon splicers join twelve fibres in one arc. On a 144 fibre joint that is twelve splices instead of 144, which is why high count builds use ribbon cable.

Splice trays and enclosures

Every splice sits in a tray in a closure or a wall box, in colour code order, with spare fibre coiled at a safe radius. Outdoor joints use sealed closures.

Pre terminated where I can

Inside data centres I specify factory terminated trunks with test reports. Installation is faster, cleaner and the loss is known before the cable arrives.

The 0.3 dB ceiling

TIA allows up to 0.3 dB for a splice, and I use that figure for worst case design. A fusion splice measuring anywhere near it gets redone.

Loss budgets

Adding up every dB before I order cable

A link works when the light that arrives is strong enough for the receiver. A loss budget adds the loss of the fibre, every mated connector and every splice, and checks the total against what the optics allow.

Building a loss budget A bar chart of loss in dB. The budget for 100GBASE-SR4 on OM4 is 1.9 dB. A link with 90 metres of fibre and two connector pairs at the standard maximum totals 1.82 dB and just fits. Adding a cross connect, with four pairs, totals 3.32 dB and fails. With low loss connectors the cross connected link totals 1.72 dB and fits. Optic budget Two panels Plus a cross connect Cross connect, low loss 0 dB 1 dB 2 dB 3 dB 1.9 dB 1.82 dB 3.32 dB: over budget 1.72 dB The optic allows 1.9 dB over 100 m Fibre: 90 m at 3.5 dB/km = 0.32 dB Two mated pairs at 0.75 dB: fits, just Four mated pairs: 1.4 dB over Low loss pairs at 0.35 dB: fits again

Swipe sideways to see the whole diagram.

Step 1
  1. The optic sets the budget. A 100GBASE-SR4 channel on OM4 allows 1.9 dB of loss over up to 100 m. Every connector and metre of fibre must fit inside it.

  2. Ninety metres of multimode at the standard maximum of 3.5 dB per km costs 0.32 dB. On short links the fibre itself is the small part.

  3. Two mated pairs, one at each patch panel, at the TIA maximum of 0.75 dB each, add 1.5 dB. The total is 1.82 dB: inside the budget with almost nothing to spare.

  4. A cross connect adds two more mated pairs. At 0.75 dB each, the link needs 3.32 dB and fails, even though it is still under 100 m.

  5. Low loss MPO connectors rated at 0.35 dB per pair bring the same cross connected link to 1.72 dB. This is why I specify low loss parts for 40G and faster.

Try it: loss budget calculator

90 m
2
0

Tight. The link fits with only 0.08 dB to spare. A dirty connector or one more patch would push it over. Clean, test, and consider low loss parts.

Fibre
0.32 dB
Connectors
1.50 dB
Splices
0.00 dB
Total loss
1.82 dB
Budget
1.90 dB
Margin
0.08 dB

The numbers I design with

ElementStandard maximumTypical modern parts
Multimode fibre at 850 nm3.0 to 3.5 dB/km, depending on the standard and editionAbout 2.5 dB/km
Multimode fibre at 1300 nm1.5 dB/kmAbout 0.6 dB/km
Single mode, indoor (OS1a)1.0 dB/kmAbout 0.35 to 0.5 dB/km
Single mode, OS20.4 dB/kmAbout 0.35 dB/km at 1310 nm, 0.2 at 1550 nm
Mated connector pair0.75 dBAbout 0.2 to 0.35 dB for low loss LC and MPO
Splice0.3 dBUnder 0.05 dB for a good fusion splice

Loss budget and power budget

The loss budget is what the cabling loses. The power budget is what the optics can tolerate: transmit power minus receiver sensitivity, less a penalty allowance. IEEE turns that into a maximum channel insertion loss for each optic.

Which connectors count

The connectors plugged into the optics at each end are part of the optic's test, so I count the mated pairs in between: panels, cassettes and cross connects.

Margin

I aim to leave at least 0.5 dB (typical) of margin on short reach multimode links and more on long single mode ones, for ageing, repairs and the dirt nobody admits to.

Too little loss

On short single mode links with long reach optics, the light can be too strong and overload the receiver. The data sheet gives a maximum receive power; an attenuator fixes it.

Testing

Clean it, test it, and keep the results

Dirt is the commonest cause of fibre faults, and testing is how I prove a link before anyone relies on it. The rule on every site I run is simple: inspect before you connect.

Inspect, clean, inspect again An inspection scope view of a connector end face, with four zones: A, the core; B, the cladding; C, the adhesive ring; and D, the contact area. At first, dirt sits across the core and the end face fails. After a dry clean, one spot remains on the cladding. After a wet then dry clean, only one embedded speck remains on the contact zone, and the end face passes. A B C D Pass criteria (IEC 61300-3-35) A, core: single mode allows no defects at all B, cladding: small scratches and spots only C and D: no longer graded in the 2022 edition Loose dirt must still be cleaned off Spots left after repeated cleaning count as embedded, which the standard accepts Fail: dirt in the core Dry clean: click cleaner Still a spot on the cladding Wet, then dry clean Pass: core and cladding clear

Swipe sideways to see the whole diagram.

Step 1
  1. I look at every end face with a camera based inspection scope before it is connected, on both sides of the mated pair. Here there is dirt across the core, so it fails.

  2. A one click cleaner or a cleaning cassette wipes the end face. Dry cleaning removes most loose dust, and it is where I always start.

  3. One spot is left on the cladding. Never assume a clean worked. The scope decides, not the cleaner.

  4. For oil or stubborn residue, I use a cleaning fluid made for fibre and finish dry straight away. Alcohol that is left to dry leaves its own film.

  5. The core and cladding are clear. The one remaining speck sits on the contact zone and has survived several cleans, so it counts as embedded and acceptable. Now, and only now, I connect.

TestToolWhen I use itWhat it proves
InspectionCamera inspection scopeEvery end face, before every connectionPass or fail per IEC 61300-3-35
Tier 1 (basic)OLTS (optical loss test set): light source and power meterEvery link at handoverLoss against the limit, plus length and polarity
Tier 2 (extended)OTDR (optical time domain reflectometer)Backbones, outside plant, any link that fails Tier 1Where each loss is: connectors, splices, bends, breaks
Fault findingVFL (visual fault locator), red light at 650 nmShort runs, patch cords, panelsBreaks and tight bends glow red

Setting the reference

An OLTS is referenced before testing, so the result includes the right connectors. TIA describes one, two and three jumper methods; the one jumper method is the one I ask for, as it includes both end connections.

Encircled flux

For multimode, how the light is launched changes the result. Test sets that meet the encircled flux launch condition give repeatable results, and I ask for it in the test specification.

Both wavelengths

I test multimode at 850 and 1300 nm and single mode at 1310 and 1550 nm. The difference between wavelengths says a lot about bends.

Results are a deliverable

Every link's test results, in the tester's native file, go into the handover pack with the drawings and the schedule. They are the baseline for every fault later.

Reading an OTDR trace

Reading an OTDR trace An OTDR trace of backscattered light against distance, above a drawing of the link: the OTDR, a launch reel, a patch panel, a splice, a tight bend, a far panel and a receive reel. The trace slopes gently down along the fibre. There is a spike and a step at each connector, a small step at the splice and a larger step at the bend. A big spike marks the end, then the trace drops into noise. Backscatter, dB distance OTDR launch reel panel splice tight bend panel receive reel Launch reel hides the dead zone Connector: spike and a step down Splice: a small step, no spike Bend: a step, bigger at 1550 nm Far connector, measured End of the fibre: big spike, then noise

Swipe sideways to see the whole diagram.

Step 1
  1. The OTDR sends pulses and measures the light scattered back. Its own connector blinds it for a few metres, the dead zone, so a launch reel of known fibre goes first.

  2. A mated connector shows as a spike, from its reflection, followed by a step down, which is its loss. Thanks to the launch reel, the first panel can be measured.

  3. A fusion splice shows as a small step with no spike, because it reflects almost nothing. Each event gets a distance, so the splice tray can be found.

  4. A tight bend is a step that grows at longer wavelengths. Testing at 1310 and 1550 nm and comparing the two tells a bend from a bad splice.

  5. A receive reel after the far panel lets the OTDR measure the last connector too. Without it, the far end would be lost in the end reflection.

  6. The end of the fibre gives a large reflection, then the trace falls to noise. The distance to it confirms the length on the drawings.

OTDR launch reels are usually hundreds of metres long. A rule of thumb from EXFO is the pulse width in nanoseconds divided by ten, in metres, plus 20%: about 600 m for a 5,000 ns pulse.

Safety

Working safely with light and glass

Fibre is safe to handle, but it carries invisible laser light and it leaves glass splinters. These are the habits I insist on wherever fibre is worked.

Invisible light

Most fibre systems use infrared light that the eye cannot see, so a live fibre looks dark. I treat every fibre as live until a power meter says otherwise.

Never look into a fibre

I never look into a fibre end or an optic port, with or without a magnifier. A camera based inspection scope shows the end face on a screen instead.

Laser classes

IEC 60825-1 sets laser classes and IEC 60825-2 covers fibre systems. Short reach optics are usually Class 1, eye safe in normal use. Red fault locators are often Class 2 or 2M, and the M means no magnifiers.

Glass shards

Cleaved fibre ends are tiny glass splinters that pierce skin and do not show on an X ray. They go straight into a marked sharps container. I work on a dark mat, with no food or drink nearby.

Chemicals

Cleaning fluids, gel from loose tube cables and isopropyl alcohol need ventilation and gloves. I check the safety data sheets on site.

Outside plant

Work in manholes, ducts and on poles has its own risks: confined spaces, traffic and height. Those jobs follow the site rules and the right permits.

PON and outside plant

Fibre beyond the building: PON, dark fibre and ducts

Outside the data centre, fibre reaches homes and businesses through passive optical networks, and links sites over leased dark fibre. A little knowledge of both helps when a branch or campus depends on them.

A passive optical network An OLT in the exchange sends light down one feeder fibre to a passive splitter, which divides it among many ONTs at homes or businesses. Downstream traffic, in purple, goes to every ONT at once. Upstream traffic, in orange, comes back from each ONT in its own time slot so they never collide. feeder fibre 1490 nm down 1310 nm up OLTin the exchange Splitter1:32, passive ONT 1at a premises ONT 2at a premises ONT 3at a premises ONT 32at a premises and so on One fibre from the exchange, shared by up to 32 or more premises through an unpowered splitter.

Swipe sideways to see the whole diagram.

Animation

Downstream, the OLT (optical line terminal) broadcasts to every ONT (optical network terminal), and each keeps only its own encrypted traffic. Upstream, each ONT transmits in time slots the OLT grants, so the orange packets arrive one after another.

TechnologyStandardDownstreamUpstreamDown wavelengthUp wavelength
GPONITU-T G.984About 2.5 Gb/sAbout 1.25 Gb/s1490 nm1310 nm
XGS-PONITU-T G.9807.1About 10 Gb/sAbout 10 Gb/s1577 nm1270 nm

Split ratios of 1:32 or 1:64 are common (typical); XGS-PON allows up to 1:128. Because the wavelengths differ, GPON and XGS-PON can share the same fibre and splitters during an upgrade.

Where I meet PON

More and more UK business and home broadband arrives over FTTP (fibre to the premises). For a branch, I care about the service it delivers and its handoff, usually Ethernet, rather than the PON behind it.

Dark fibre

Dark fibre is leased glass with no service on it: I light it with my own optics. It suits data centre interconnects and campuses, and its loss and length decide the optics.

Outside plant

Between buildings, cable runs in ducts, chambers and joints. I design for spare ducts, diverse routes for resilient links, and sealed, labelled joint closures.

Diverse routes

Two fibres in the same duct are one digger away from failing together. For resilient sites I ask carriers for route maps and separate building entries. More on this is on the WAN (wide area network) page.

Troubleshooting

Finding a fibre fault from end to end

Fibre faults come down to a short list: dirt, polarity, the wrong fibre or connector, bends, breaks, and optics that do not match. Choose a symptom to see where it usually sits and what I do first.

A fibre fault finder Five places a fibre fault can sit, in order: the optic, the patch cord, the panel, the permanent link and the far end. For each symptom, test light travels as far as the place that fails, and a panel shows what I see and what I do first. Opticboth ends Patch cordend faces, type Paneladapters Permanent linksplices, bends Far endoptic, cord What I see What I do first Symptom: Errors climb after a move Receive power 2 to 3 dB lower than its baselineshow interfaces transceiver detail Symptom: No light on a new link No receive power at either endSwap the pair at one patch cord Symptom: Loss jumped after a repatch Receive power about 4 dB lower than beforeRead the print on every cord Symptom: High loss at one panel OTDR shows a large reflective event thereCheck every adapter: blue or green Symptom: Loss worse at 1550 nm Loss at 1550 nm well above loss at 1310 nmOTDR at both wavelengths Symptom: Errors on a short single mode link Receive power above the optic's maximumFit an in line attenuator Symptom: Light both ways, no link Both ends report receive power, the port stays downshow interfaces transceiver (both ends) Symptom: Total loss of light No light; OTDR end event short of the far endOTDR, then VFL near the event

Swipe sideways to see the whole diagram.

Dirty connector. The commonest fault of all. I inspect both ends of the mated pair, clean, inspect again and compare receive power with the baseline from handover.

Polarity. Transmit is meeting transmit. If neither end sees any light and both optics show transmit power, I count the crossings and swap the pair at one cord.

Mixed fibre types. A 62.5 µm cord in a 50 µm link, or a multimode cord on single mode, loses several dB. I read the jacket print, not the colour.

UPC mated to APC. The angled face meets a flat one, leaving an air gap. Loss is high and the end faces can be damaged, so I inspect both after correcting it.

A macrobend. A cable trapped by a door, a tight tie or an overfilled tray. The OTDR gives the distance; a VFL shows the glow on short runs.

Receiver overload. A long reach optic on a few metres of fibre can deliver more light than the receiver accepts. A fixed attenuator, sized from the data sheet, fixes it.

Mismatched optics. LR at one end and FR at the other, different wavelengths, or a different FEC (forward error correction) setting. I compare the optic type and settings at both ends.

A break. The OTDR end event gives the distance to the break, which I match to the route drawings. Then the repair: a splice in a new closure, and a fresh test.

Animation

The commands I start with

PlatformCommandWhat it shows
Cisco IOS XEshow interfaces transceiver detailTemperature, voltage, bias, transmit and receive power, with thresholds
Cisco NX-OSshow interface ethernet1/1 transceiver detailsThe same, per lane on multi lane optics
Arista EOSshow interfaces transceiverOptical power and temperature for every port
Juniper Junosshow interfaces diagnostics optics et-0/0/0Power per lane, with alarm and warning flags
Linuxethtool -m eth0The module's identity and DOM readings

I compare receive power with the baseline recorded at handover. A drop of a few dB on a link that used to be fine is almost always a connector. My general method is on the troubleshooting page, and the terms are in the glossary.

Projects

Where I use it

My home lab runs on copper, so my fibre work comes from data centre, campus and estate projects. Fibre decisions sit inside most of them: which grade, which optics, how much spare, and how it is tested before handover.

2e2 · 2011 to 2013

A data centre from an empty shell

Delivered the £25M Network Rail data centre build from an empty shell, covering structured cabling, building management systems and mechanical and electrical integration.

XIDA · 2025 to now

AI ready data centre infrastructure

Designed AI ready data centre infrastructure for high density compute clusters, covering network, power, cooling and structured cabling, with the rack layouts and deployment documentation the build teams worked from.

XIDA · 2021 to 2024

Cabling for high performance workloads

Prepared data centre infrastructure for high performance workloads: rack allocation, structured cabling pathways and deployment coordination.

Manx Telecom · 2016

A Tier 3 data centre

Tier 3 data centre and managed infrastructure for over 300 customer sites on Cisco ACI (Application Centric Infrastructure) and Nexus.

BNY Mellon · 2018 to 2019

A refresh across Europe, the Middle East and Africa

Audit, high and low level design and implementation of LAN (local area network), WAN, SD-WAN and data centre infrastructure, replacing end of life equipment with minimal impact on global operations.

Training · structured cabling

Fibre and copper cabling

I have trained in fibre and copper structured cabling, alongside power and electrical systems, which is the grounding behind the cabling decisions on this page.

The physical layer behind every link: copper is on the copper cabling page, and trunks, breakouts and switch optics are on the data centre cabling page. See all credentials