Hyperscale pods

One estate, built from pods

I wrote a vendor neutral reference architecture for hyperscale pods: foundations, nine domain designs and an overarching design. This page shows how it fits together, from the hall to the service, for the engineers who build it and the people who fund it.

  • Pod model
  • Pod families
  • Service tiers
  • Failure domains
  • Cyber recovery vault
  • Change in waves
  • Acceptance gate
  • Pod lifecycle
Two sites built from pods, with copies pulled to a vault Two sites in a region, each with two halls of pods. Data replicates between the sites, and an isolated vault pulls its own copies from both. Site A Site B Vaultpulls copies
Live view · two sites, pods in every hall, copies pulled to the vault
In short

What is a hyperscale pod architecture?

A hyperscale pod architecture builds a large estate from pods: repeatable units of racks, network, storage, management and power, built in a factory, run as one unit and retired whole. Each pod belongs to a family, such as general compute, containers or AI, and every family uses the same kinds of block. A service's tier decides how many pods, halls and sites it spans, and every layer, from facilities to operations, carries out the same pattern.

Key facts

  • A pod sits inside one hall and one power and cooling block, and joins the hall through a small, standard set of interfaces.
  • Seven pod families cover general compute, containers, data, storage services, accelerated AI work, the isolated vault and management.
  • Typical service tier targets run from back within 15 minutes with no data lost for the most critical tier to within 24 hours for the least.
  • Failure domains run in seven levels, from a single part to a whole region, and each level is held by the one above it.
  • Each region keeps an isolated vault that pulls its own immutable copies and shares no identity, management or network path with production.
  • A pod passes ten stages from demand to retirement, and each stage ends in a gate with evidence.
Overview

The estate as one system

I treat a large estate as one system made of pods. Every layer, from the halls to the services, is designed together, and every pod is built from the same kinds of parts. Each layer below links to the page that holds its detail.

The layers of a pod estate, from the halls to the services Facilities at the bottom, then the network, then compute, storage and AI pods side by side, then platforms and services. Security and operations run through every layer, and the lifecycle runs underneath all of them. The estate in layers Facilitieshalls, power and cooling blocks, liquid ready Networkpod fabrics, hall core, site links, out of band Computeserver profilesStorageperformance classesAI podsaccelerated families Platformsvirtual machines, Kubernetes and bare metal, one interfaceServicesbusiness services, each with a tier SecurityzonesidentitykeysOperationstelemetrythe recordchange lifecycle underneath: catalogue, factory, supply, ownership and retirement

Swipe sideways to see the whole diagram.

Step 1
  1. The halls come first: space, power and cooling, set out in blocks. Every other layer needs a position, two power feeds and the right cooling before it can arrive.

  2. The network joins racks into pod fabrics, pods into a hall core and halls into a site. A separate out of band network gives a way in when production is down.

  3. Compute, storage and accelerated pods sit side by side on the network. Each comes in a few fixed profiles, so every pod of a kind is built the same way.

  4. Platforms turn hardware into virtual machines, Kubernetes or whole servers behind one interface. Services run on top, each with a tier that says how critical it is.

  5. Security and operations are not layers added later. Zones, identity, keys, telemetry and the record reach every layer, including the out of band network.

  6. Lifecycle runs under it all: a catalogue to order from, a factory to build in and a planned end for every pod. That stops the estate filling with kit nobody owns.

One pattern, carried out by every layer

A critical service is only as resilient as its weakest layer. The service tier is the contract that makes facilities, network, storage, platform and operations do their part of the same pattern.

The joins are where estates fail

Most of what goes wrong in a large estate sits between teams: a port speed one side assumed, a shared service nobody owned, a change pushed everywhere at once. So the design spends as much effort on the joins as on the parts.

Build for the long run, fit out for the near term

Halls are sized for many years of growth, but fitted out one block at a time as demand arrives, so spending follows demand instead of a forecast.

The pod

What a pod is, and what every pod shares

A pod is a repeatable unit of capacity: a fixed set of racks, servers, network, storage, management and power distribution, built in a factory to one design, delivered whole, run as one unit and retired as one unit.

Anatomy of a pod, built up one part at a time Four compute racks, each with two top of rack switches and an out of band switch. A network and management rack joins them in a pod fabric with uplinks to the hall core and the out of band network. A storage rack sits beside them, and every rack takes two power feeds from separate paths, A and B. One pod built in a factory, delivered whole, retired whole computecomputecomputecompute two top of rack switches and an out of band switch in every rack network andmanagementHall corethe hall networkOut of bandits own network storage power path Apower path B

Swipe sideways to see the whole diagram.

Step 1
  1. Each compute rack holds servers to the family's profile. The number per rack is set by the power the zone can deliver, not by how many fit.

  2. Every rack has two top of rack switches, so one can fail or be upgraded, and its own out of band switch for the management ports.

  3. A network and management rack joins the racks into a pod fabric, and connects the pod to the hall core and the out of band network.

  4. Storage sits in the pod, in its own rack or as local drives, or the pod connects to a shared storage services pod in the same hall.

  5. Every rack takes two feeds from different power paths, A and B, so either path can fail or be maintained without a pause.

  6. The whole pod is built and tested in a factory, delivered as racks, and joined to the hall through a small, standard set of interfaces.

Three tiers of standard
TierRuleExamples
Must be commonEvery pod follows it. A difference needs an approved exception and a date to close it.The link to the hall core, out of band management, power feeds and rack positions, security zones, naming, the as built record, lifecycle gates
Common by defaultEvery pod uses the default unless a recorded reason is approved, which is quick.Server network speed, top of rack model, rack type, storage pattern, build automation, server generation
Specific to the familySet in the family design, with no exception needed.Server profile, accelerators, application stack, acceptance tests, capacity plan

A pod never spans halls

A pod sits inside one hall and one power and cooling block. If a block is lost, the pods inside it are lost together, and nothing else is.

Built before it ships

Racks are integrated, cabled, loaded with firmware and burned in at a factory. The site only places, connects and accepts them. My design authority page covers the factory model.

Pod families

Seven families, one set of blocks

Every pod is one of seven families. Each family is a fixed mix of the same kinds of block, so a new pod of a family is a repeat, not a new design.

Seven pod families built from six kinds of common block Six kinds of block on the left: compute profile, rack type, network ports, storage class, platform and security zone. Seven family cards on the right, each made from the same six blocks: general, container, data, storage services, accelerated, isolated and management. A request picks a family and a size, and the blocks follow. Common blocks Seven pod families compute profilerack typenetwork portsstorage classplatformsecurity zone Generalvirtual serversstandard zoneshared storageContainerKubernetesstandard zoneobject storage Datadata platformshigh densitylocal drivesStorageblock and fileand objectfor the hall AcceleratedAI and GPU workdense or liquidback end fabric Isolatedthe vaultown cageown identityManagementnames and timekeys and logsone per site Requesta family anda sizethe blocks follow every family is a fixed mix of the same six kinds of block

Swipe sideways to see the whole diagram.

Step 1
  1. Every pod is built from six kinds of block: a compute profile, a rack type, network ports, a storage class, a platform and a security zone. The domain designs set the choices for each.

  2. General compute pods run virtual machines. Container pods run Kubernetes at scale. Both sit in the standard zone and use shared storage.

  3. Data pods carry storage heavy platforms on local drives in the high density zone. Storage services pods give each hall its shared block, file and object storage.

  4. Accelerated pods carry AI training and inference, with their own back end fabric, in the high density or liquid zone.

  5. Isolated pods hold the cyber recovery vault, in their own cage with their own identity. Management pods give each site its names, time, keys, logs and automation.

  6. A request picks a family and a size from the catalogue. The blocks follow, so nobody designs a pod from scratch.

What each family is for
FamilyWhat it is forWhere it lives
General computeVirtual machines and general workloadsStandard zone
Container platformKubernetes at scaleStandard zone
Data and analyticsScale out data platforms, storage heavyHigh density zone
Storage servicesBlock, file and object storage as a shared service, one pod in each hallStandard zone
AcceleratedAI training and inferenceHigh density or liquid zone
IsolatedThe cyber recovery vault and regulated enclavesIts own cage and security zone
ManagementNames, time, directory, certificates, keys, monitoring and automation for one siteStandard zone, one per site

A few sizes, each inside one block

Each family comes in a few sizes. Every size is set so that the whole pod fits inside one power and cooling block of its zone.

The catalogue is how people choose

Each family and size is a catalogue entry with a price, a lead time, the tiers it supports and an end of life date, so a business can compare options and fund its own capacity.

Placement

How a service lands on the estate

A team never asks for a server. It asks for a catalogue entry and says how critical the service is. From there every step follows rules, and the tier chosen first decides each one.

How a service lands on the estate, in six steps Six boxes in a loop: request, place by tier, secure and connect, store and host, observe, and run and renew. From the second step on, each box carries a tier badge, because the tier set at the request decides every step after it. Requesta catalogue entryand a service tier Place by tierpods, halls and sitesset by the tierT Secure and connectzone, addresses andpolicy from codeT Store and hoststorage class, copies,platform through an APIT Observeobjectives, telemetry,alerts before trafficT Run and renewshowback, patching,refresh and retirementT the tier chosen at the start sets every step after it

Swipe sideways to see the whole diagram.

Step 1
  1. A team picks an entry from the catalogue, such as a container platform of a given size, and sets the service tier. The tier is fixed before anything is placed.

  2. The tier decides where the service runs: one pod, a second hall, or active in both sites of a region. Placement follows rules, not negotiation.

  3. The service goes into a security zone. Its addresses and network policy come from the source of truth, so nobody types them on a device.

  4. Storage class and copies follow the tier. The platform creates the project, namespace or hosts through its API (application programming interface), with no tickets for standard requests.

  5. Objectives, telemetry, alerts and runbooks are live before the first user arrives. A service nobody can see is not ready.

  6. Costs are shown to the owner each month. Patching and refresh run in waves, and the service has a planned end, like the pod under it.

No layer gives less than the tier

If the network, storage or platform cannot give a service what its tier needs, the service does not get that tier. Changing a tier means placing the service again.

Shared services from its own site

Names, time, identity, certificates and secrets come from the management pod in the service's own site, with local caches, so a fault in one site cannot stop the other.

Service tiers

One pattern per tier, carried out by every layer

Four service tiers cover everything from the most critical payment or trading system to a reporting tool. Pick a tier to see where its service runs and how its data is copied.

Where a service runs in each of the four service tiers Two sites in a region, each with two halls. Tier 0: active pods in both sites with a synchronous copy and a vault copy. Tier 1: active in one site with a standby pod in the other and an asynchronous copy. Tier 2: one pod with spare capacity and a replica or backup in the other hall. Tier 3: one pod, rebuilt from code and backup. Site A Hall 1 Hall 2 Site B Hall 1 Hall 2 two sites in a region, joined by routed links only activeserving activeservingsynchronous copyvault copy standbyreadyasynchronous copy sparecapacityreplicaor backup backupcheckedrebuilt from code and backup

Swipe sideways to see the whole diagram.

Tier 0. Active in pods in both sites of a region, and both sites announce the service. Storage copies every write to the other site before confirming it, and the vault keeps its own copy. Typical target: back within 15 minutes, with no data lost.

Tier 1. Active in one site, with a standby pod ready in the other. Storage replicates asynchronously, so a few minutes of data can be lost. Typical target: back within an hour, with under 5 minutes of data lost.

Tier 2. One pod, with spare capacity in another hall or site and a replica or backup in the other hall. The platform rebuilds from code. Typical target: back within 4 hours, with under an hour of data lost.

Tier 3. One pod, rebuilt from code and restored from backup, with every backup checked automatically. Typical target: back within 24 hours, with under 24 hours of data lost.

Animation
The four tiers at a glance
TierTypical recovery timeTypical data lossWhere it runsHow it is proved
Tier 0Under 15 minutesNoneActive in pods in both sites of a regionPlanned failovers between sites
Tier 1Under 1 hourUnder 5 minutesActive in one site, standby pod in the otherPlanned failovers between sites
Tier 2Under 4 hoursUnder 1 hourOne pod, spare capacity in another hall or siteRestore tests on a schedule
Tier 3Under 24 hoursUnder 24 hoursOne pod, rebuilt from code and backupBackups checked automatically

Typical targets. Each organisation sets its own from the impact tolerances of its important business services, which my resilience page explains.

The tier is a contract

Every layer has a part to play for each tier. If one layer cannot do its part, the service does not meet its tier, however good the others are.

Tier honestly

Tier 0 costs far more than Tier 3, because it runs active in two sites. I ask for a reason behind every Tier 0 service, because an estate where everything is critical is an estate where nothing can be afforded.

Failure domains

Small failures stay small

A failure domain is everything one fault can take out. I design seven levels, from one part to a whole region, and make sure each level is held by the one above it.

Seven failure domain levels, from one part to a region Nested boxes grow from a single part to a node, a rack, a pod, a hall, a site and a region. Beside them, each level lists what typically fails and what a service sees. A part changes nothing and a node restarts work. A rack leaves less capacity, a pod moves services to another pod, and then come the other hall, the paired site and recovery in another region where the rules allow. Seven levels, each held by the next region site hall pod rack node part Parta fan, optic or disk: users see nothing Nodea server or leaf: work restarts in the pod Rackrack power or a leak: less capacity Podfabric or cluster: move to another pod Hallpower or cooling: use the other hall Sitea site event: run from the paired site Regiona regional event: recover where rules allow

Swipe sideways to see the whole diagram.

Step 1
  1. A failed fan, optic or disk changes nothing a user can see. A failed server or leaf switch restarts work inside the same pod.

  2. Losing a rack, through its power or a leak, leaves the pod running with less capacity. That is why every pod is sized to lose a rack.

  3. A pod is the unit of failure as well as the unit of build. If a whole pod fails, services move to another pod, because nothing stretches across two.

  4. Each hall's power and cooling zones line up with its pods. If a hall is lost, the most critical services run from the other hall or site.

  5. Each site runs alone, with its own management pod and out of band network. If a site is lost, services carry on from the paired site in the region.

  6. A regional event is the largest domain. Recovery in another region is planned only where the rules on data allow it.

What fails at each level, by domain
LevelFacilitiesNetworkCompute and storageWhat a service sees
PartA fan or power supplyAn opticA disk or memory moduleNothing
NodeA rack power feedA leaf switchA server or controllerA restart inside the pod
RackRack power or a leakA leaf pairA rack of serversLess capacity in the pod
PodA block's distributionThe pod fabricThe pod's storageFailover to another pod
HallA hall's cooling or power zoneThe hall coreEvery pod in the hallRun from the other hall
SiteA utility or site eventSite linksEvery pod at the siteRun from the paired site
RegionA regional eventLinks between regionsEvery siteRecover elsewhere, where rules allow

One change cannot reach every pod

Changes run in waves, pod by pod, so one bad change hurts one pod first and stops there.

Two versions, not one

A single firmware or software version everywhere means one defect can stop every pod at once. Two versions, staggered, keep part of the estate on known good code.

No layer 2 between sites

Sites are joined only by routed links. A broadcast storm or loop in one site cannot reach the other.

A way back in

Each site has its own out of band network, with its own switches, circuits and power, so engineers can still reach the kit when production is down.

Site independence

Each site runs alone

Two sites in a region only protect each other if neither secretly depends on the other. Each site has its own management pod, shared services, key services and out of band network, so losing one leaves the other whole.

What happens across the estate when a site is lost A timeline from the moment a site is lost. Within minutes the operations centre declares an incident. Tier 0 services carry on from the other site with no data lost. Tier 1 moves to standby pods within an hour, Tier 2 is restored within four hours and Tier 3 is rebuilt within a day. When the site returns, services move back in waves. Typical recovery after losing a site not to scale 0 to minutessite lost,incident calledoperationsdeclares it 15 minutesTier 0 runs on,no data lostalready activein both sites 1 hourTier 1 movesto standby podsplatformand storage 4 hoursTier 2 backin other siteplatformand storage 24 hoursTier 3 rebuiltfrom backupplatformand storage Aftersite returns,move backevery domainin waves

Swipe sideways to see the whole diagram.

Step 1
  1. A site goes dark through a utility failure or a site event. Alarms fire, the operations centre declares an incident, and any regulatory reporting clock starts.

  2. Tier 0 services carry on from the other site within minutes and lose no data, because they were already active there. Nobody has to fail them over.

  3. Tier 1 services move to their standby pods in the other site, typically within an hour, using the asynchronous copies.

  4. Tier 2 services are restored in the other site from replicas or backups into spare capacity, typically within four hours.

  5. Tier 3 services are rebuilt from code and restored from backup, typically within a day.

  6. When the site is back, services move home in waves, not all at once, and the lessons go into the designs and the runbooks.

Find the hidden shared service

The classic trap is a directory, name or time service that lives in one site while both sites quietly depend on it. I map those dependencies before the second site is built, and my resilience page shows what each one takes down.

Practise the bad day

Failovers between sites, rebuilds in the vault, handovers between operations centres and repairs with the production network down all run on one published calendar, with the evidence kept.

Halls and blocks

Build the hall once, fit it out by block

A hall is built for many years of growth but fitted out one power and cooling block at a time. Pods sit inside the block that powers and cools them, so each block is also a failure domain.

A pod hall fitted out one block at a time A hall split into four power and cooling blocks, with the hall network racks across the middle. The first standard block is fitted with general, container, storage and management pods. A high density block takes data and inference pods. The second standard block is fitted as demand grows, and the liquid ready block is fitted only when a liquid cooled pod is ordered. example: 2 MW in four blocks of 500 kW (indicative) One hall, built for the long run Block 1: standard Block 2: standard Block 3: high density Block 4: liquid ready hall network racks, fitted with the hall Block 1: standardgeneralcontainerstoragemanagement Block 3: high densitydatadatainference Block 2: standardgeneralcontainerisolated Block 4: liquid readyrack scale AIliquid cooledfitted when ordered

Swipe sideways to see the whole diagram.

Step 1
  1. The hall is built for the long run: the room, its main plant routes and four power and cooling blocks. Only what demand needs now is fitted.

  2. The hall network racks go in with the hall, before any pod, so every pod arrives to the same standard connection.

  3. The first standard block is fitted and filled with general, container, storage and management pods. Each pod sits inside one block, never across two.

  4. A high density block takes data platforms and inference pods, with rear door or liquid cooling sized for them.

  5. The next standard block is fitted when the first passes a set level of use, so fitted power stays one block ahead of committed demand.

  6. The liquid ready block has its pipework routes and space from day one, but is fitted only when a liquid cooled pod is ordered.

Two of three power systems

Each rack takes power from two of three UPS (uninterruptible power supply) systems, so any one system can fail or be maintained without a pause. My facilities page explains the power chain.

Cooling chosen by zone

Air with hot aisle containment for standard racks, rear door heat exchangers for denser ones, and direct liquid cooling for the densest. Cooling keeps running through a power cut.

Room to replace in place

Each hall keeps space for a pod of each family it hosts to be replaced beside the old one, so a refresh never needs a migration across halls.

Prefabricated plant

Power and cooling plant can arrive as factory tested skids, so halls are built the way pods are: in a factory, then placed and connected.

Cyber recovery

A vault the attacker cannot reach

Replicas and backups protect against failures, but an attacker with administrator rights can corrupt them too. So each region has an isolated vault and a clean room that share nothing with production.

An isolated vault that pulls its own copies, and a clean room to rebuild in Production holds services with immutable snapshots, a replica at the other site and a backup in another hall. The vault, in its own zone, pulls copies through a gate it controls, scans them and locks them as immutable copies. An attacker in production has no identity, management or network path to the vault. Critical services are rebuilt from vault copies in a clean room. Production Isolated vault Servicesin podsSnapshotsimmutableReplicaat the other siteBackupin another hall Gatepulls copies through its own gate Scanfor malwareLocked copyimmutableOwn identity and keys Attackerwith admin rightsno shared identity, management or network path Clean roomrebuild critical services

Swipe sideways to see the whole diagram.

Step 1
  1. Production keeps its own copies in layers: immutable snapshots on the arrays, a replica at the other site and a backup in another hall. They cover mistakes and failures.

  2. The vault reaches out through a gate it controls and pulls copies of critical data. Production cannot push to it, sign in to it or even see it.

  3. Each copy is scanned, then locked as an immutable copy that nobody can change or delete before its retention ends.

  4. An attacker with administrator rights in production can corrupt production and its online copies. The vault shares no identity, management or network path, so it stays clean.

  5. Critical services are rebuilt from vault copies in a clean room, checked, then brought back. Rebuild drills run on a calendar, because an untested vault is only a hope.

Copies by the 3, 2, 1, 1, 0 rule

Three copies of the data, on two kinds of media, one at another site, one immutable or offline, and zero errors when restores are checked.

Its own identity and keys

The vault has its own sign in, its own administrators and its own keys. Nothing an attacker steals from production opens it.

A clean room to rebuild in

A small, separate environment where critical services are rebuilt and checked before they rejoin the estate, so a hidden infection is not restored with them.

Models and data count too

Training data and model weights are protected like any critical data, and the most valuable models are kept in the vault.

Change and the record

Change in waves, from one source of truth

Every network, platform and policy change starts as data, runs through a pipeline and reaches the estate in waves. One record says what exists and who owns it.

A change moving from the source of truth through a pipeline to the estate in waves A change starts in the source of truth, passes through a tested pipeline and a lab, then reaches one canary pod, then waves of more pods. An error budget gauge shows the next wave waiting when the budget is nearly spent. One record, checked against discovery every night, tracks every pod. Source of truthintent as data Pipelinetest and review The estate canary wave 1 wave 2 wave 3 Labfirst proof error budgetnearly spent: the next wave waits One recordchecked nightlydiscovery compares it with reality

Swipe sideways to see the whole diagram.

Step 1
  1. Every change starts as data in the source of truth: what the network, platform or policy should be. Nobody types configuration into a device.

  2. The pipeline generates the configuration, tests it and sends it for peer review. Only a change that passes reaches anything real.

  3. It runs in the lab, then on one canary pod. If the canary misbehaves, the change stops there.

  4. Then it spreads in waves: a few pods, then more. No change ever reaches every pod at once, so one mistake cannot take the whole estate down.

  5. Each tier has an objective and an error budget, the downtime it may use. When a budget is nearly spent, the next wave waits and risky change pauses.

  6. Every change updates one record of what exists and who owns it. Discovery checks it against reality every night, and gaps are fixed, not ignored.

Error budgets decide the pace

An objective of 99.9 percent allows about 43 minutes of downtime in a 30 day month. That allowance is the budget: while it lasts, teams ship; when it is spent, they stabilise.

Record before power on

Nothing powers on until it is in the record, built from the build data. A record that is wrong leads to the wrong change or a failed recovery.

Runbooks as code, AI that assists

Known faults get automatic fixes, within limits. Everything else goes to a person, with the runbook and the evidence already gathered.

Pipelines for every layer

The same pattern covers network, platform and policy. My automation page shows the network pipeline step by step.

Interfaces and acceptance

The joins between teams, written as contracts

Wherever two domains meet, I write the interface down with an owner and agreed values on both sides. A pod goes live only when every domain has passed it at one acceptance gate.

Domain teams joined to a pod by interfaces, and one acceptance gate A pod in the middle, with nine domains around it: facilities, network, compute, storage, platform, security, operations, lifecycle and AI pods. Lines show the interfaces between them, such as power and position, and build data. Each domain signs off its part, and only then does the pod pass the gate and go live. Podone family, one owner Facilities Network Compute Storage Platform Security Operations Lifecycle AI pods power and positionbuild dataclasses and copieszones and keys an owner and agreed values on both sides ✓✓✓✓✓✓✓✓✓ Gateevery domain has signed: the pod goes live

Swipe sideways to see the whole diagram.

Step 1
  1. Nine domain teams touch every pod: facilities, network, compute, storage, platform, security, operations, lifecycle and, for AI families, the AI pod team.

  2. Wherever two domains meet there is an interface: rack power and position, storage classes and copies, build data, zones and keys.

  3. Each interface is written down with an owner and agreed values on both sides. A change on one side is a change to both, so nothing drifts quietly.

  4. At acceptance, every domain tests its part of the pod against its own checklist, with pass marks rather than opinions.

  5. The pod goes live only when every domain has passed it. One missing signature, and the pod waits, however urgent the demand.

Examples of interfaces between domains
BetweenWhat is agreedIf it drifts
Facilities and computePower per rack, positions, weight and cooling typeRacks arrive that the floor cannot power or carry
Network and computePort speeds, optics, cabling and the out of band portServers that cannot connect on day one
Compute and platformBuild data and the firmware baselineServers that build differently in each pod
Every domain and operationsTelemetry, alerts, runbooks and the recordA pod that is live but cannot be seen
Security and every domainZones, identity, keys and certificatesServices that cannot read their encrypted data

A design authority owns the set

One design authority keeps the foundations, the family designs and the interfaces in step. My design authority page covers how that board works.

Suppliers sign up to the design

Each design's duties go into supplier contracts: signed firmware, software bills of materials, vulnerability handling and the interfaces they must meet.

Pod lifecycle

Ten stages, ten gates

Every pod lives the same life, from the request that creates it to the certificate that retires it. Each stage ends in a gate, and each gate needs evidence, not a promise.

The ten stages of a pod's life, each ending in a gate Ten stages around a ring: demand, design, order, factory build, site ready, install, acceptance, operate, evergreen and retire, with a gate between each. Retirement returns the freed space to the hall plan. A pod's life Demand Design Order Factory build Site ready Install Acceptance Operate Evergreen Retire Every stage ends in a gate with evidence kept in the record freed space returns to the hall plan

Swipe sideways to see the whole diagram.

Step 1
  1. A business asks for capacity against a catalogue entry, with an owner, a cost centre and an end date. The family design is applied to this pod: size, site, hall, zone and addresses.

  2. Hardware is ordered against the bill of materials, inside the order window. At the factory the racks are integrated, cabled, loaded with firmware and burned in.

  3. The site gets positions, power, cooling, ports and the security zone ready. The pod is delivered, recorded before power on, installed and connected.

  4. Functional, performance and resilience tests run against pass marks, and telemetry must be live. This is the one gate where every domain signs.

  5. In service, the pod is monitored, patched and checked each year for its owner and use. Capacity is added as whole racks of the same design.

  6. At the end, workloads move, data is destroyed on site, kit is reused before it is recycled, and the space goes back to the hall plan, not to the next queue.

An owner and an end date from day one

No pod moves past demand without a named owner, a cost centre and an end date. A pod past its end date shows a holding cost to its owner every month.

Telemetry before go live

A pod is not live until its telemetry, alerts and runbooks are live. Acceptance tests the operations as well as the hardware.

Order windows and two makers

Parts come from two qualified makers per category, ordered inside windows set by each family's generation plan, with buffer stock for long lead items.

Reuse before recycling

Drives are wiped or destroyed on site with certificates in the record. Kit is reused where it can be, then recycled, and embodied carbon counts when buying.

The domains

Nine domains, one design

Each domain has its own design, built on the same foundations, the same pod model and the same tiers. These are a few of the choices in each, with a link to the page where I explain the technology underneath.

Facilities

Halls in power and cooling blocks. Each rack fed from two of three UPS systems. Cooling chosen by zone, and liquid ready from day one. More on my data centre facilities page.

Network and out of band

A leaf and spine fabric in every pod, joined by a hall core. One routed network per security zone. No layer 2 between sites, and a separate out of band network. More on my data centre networks page.

Compute

One server profile per family. Servers managed only through Redfish, the standard server management interface, on the out of band network, proving their firmware before they join a pod. Two generations and two makers at a time. More on my servers and virtualisation page.

Storage and data protection

Storage designed by performance class, not by product. Storage services pods in each hall. Copies in layers, and an isolated vault in each region. More on my private cloud and storage page.

Platform

One platform cluster per pod, never stretched. Virtual machines, Kubernetes and bare metal behind one API. Signed images, rebuilt rather than patched. More on my private cloud page.

Security

Zero trust inside zones, with firewalls where zones meet. Three admin tiers with no standing rights. Keys in hardware security modules in each site, and a post quantum plan. More on my security page.

Operations and observability

Regional operations centres that hand over around the clock. Error budgets that gate change. OpenTelemetry from every layer, and one record checked every night. More on my support and service management page.

Lifecycle, factory and commercials

A catalogue entry for every family and size. Factory built pods. Two qualified makers per category, and an owner, a cost and an end date for every pod. More on my design authority page.

Accelerated and AI pods

AI as a pod family: inference in the owned halls, large training where the liquid capacity is. A separate back end fabric, and checkpoints sized to the failure rate. More on my AI infrastructure page.

Where AI fits

AI is a pod family, not a separate estate

Accelerated pods use the same halls, network standards, security zones, record and lifecycle as every other pod. What changes is where each kind of AI work runs.

Where each kind of AI work runs
WorkWhere it runsWhy
InferenceOwned halls, in pods of eight GPU servers in the high density zoneSteady demand, close to the data and the users
Fine tuningOwned halls, on the same inference podsModerate, scheduled jobs that share the GPUs
Large trainingRack scale pods in a liquid block, or at a colocation site with liquid hallsNeeds liquid cooling and large, swinging power loads
Short burstsPublic cloudPay only while the job runs

The racks, rows and acceptance tests for these pods are on my AI infrastructure page.

Utilisation is the cost

GPU hours are shown back to each team, with quotas, priorities and a utilisation target, because an idle GPU is the most expensive thing in the hall.

Checkpoints sized to the failure rate

Training is made resilient by checkpoints, and the interval comes from how often GPUs fail at that scale. Inference is made resilient by its service tier.

Models are crown jewels

Models are signed and kept in a registry, tenants are isolated, and the most valuable model weights are copied to the vault.

Short lives, planned

Accelerated pods age fastest. They get shorter lives and generation plans, with older generations moved to inference before they are sold or recycled.

Common questions

Common questions about Hyperscale pods

Short answers that stand on their own. Each one links to the section above that explains it in full.

What is a pod in a data centre?

A pod in a data centre is a repeatable unit of capacity: a fixed set of racks, servers, network, storage, management and power distribution, built to one design. It is built and tested in a factory, delivered whole, run as one unit and retired as one unit. A pod sits inside one hall and one power and cooling block, and joins the hall through a small, standard set of interfaces.

Full section: The pod

Why build a data centre estate from pods?

Building an estate from pods turns growth into repetition. Each new pod of a family is a copy of a tested design, so it is quicker to order, build, accept and support, and it fails in a known way. Pods also give clear failure domains, clear owners and clear end dates, so capacity is added, refreshed and retired in whole units rather than server by server.

Full section: Estate

What are pod families?

Pod families are the few standard kinds of pod an estate is built from. In my reference architecture there are seven: general compute, container platform, data and analytics, storage services, accelerated, isolated and management. Each family is a fixed mix of the same six kinds of block: a compute profile, a rack type, network ports, a storage class, a platform and a security zone.

Full section: Families

What are service tiers in infrastructure design?

Service tiers set how critical a service is and what every layer must do for it. Typical targets run from Tier 0, active in both sites and back within 15 minutes with no data lost, to Tier 3, rebuilt from code and backup within a day. The tier is set before a service is placed, and network, storage, platform and operations each carry out their part of the same pattern.

Full section: Service tiers

What is a failure domain?

A failure domain is everything a single fault can take out. I design seven levels: a part, a node, a rack, a pod, a hall, a site and a region. Each level is held by the one above it, so a failed disk changes nothing a user sees, a failed pod moves services to another pod, and a lost site leaves the paired site running.

Full section: Failure domains

What is a cyber recovery vault and clean room?

A cyber recovery vault is an isolated store that pulls its own immutable copies of critical data and shares no identity, management or network path with production. If an attacker with administrator rights corrupts production and its online copies, the vault stays clean. A clean room is a separate environment where critical services are rebuilt from vault copies and checked before they return.

Full section: Vault

Why roll out infrastructure changes in waves?

Rolling out changes in waves stops one mistake from reaching the whole estate. A change runs in a lab, then on one canary pod, then on a few pods, then on more. If a wave misbehaves or a service's error budget is nearly spent, the next wave waits. No change ever reaches every pod at once, so a bad change hurts one pod first and stops there.

Full section: Change

What is an acceptance gate for a pod?

An acceptance gate is the single check a pod must pass before it goes live. Every domain, from facilities and network to security and operations, tests its part of the pod against its own checklist with pass marks. Telemetry, alerts and runbooks must be live too. The pod goes live only when every domain has passed it, however urgent the demand.

Full section: Interfaces

What are the stages of a pod's lifecycle?

A pod's lifecycle has ten stages: demand, design, order, factory build, site readiness, install, acceptance, operate, evergreen and retire. Each stage ends in a gate with evidence. A pod gets an owner, a cost centre and an end date at the start, is recorded before it powers on, and at retirement its data is destroyed on site and its space returns to the hall plan.

Full section: Lifecycle

Where should AI training and inference run in a pod estate?

In a pod estate, AI is a pod family rather than a separate estate. Inference and fine tuning run in the owned halls, on pods of eight GPU servers in the high density zone, close to the data and users. Large training runs on rack scale pods in a liquid cooled block or at a colocation site with liquid halls, and short bursts can run in the public cloud.

Full section: AI pods

Engagement

How I run a hyperscale pods engagement, from estate to first pod

A pod estate is a long programme, so I start with the standards and the joins between teams before any hardware is chosen. Then every pod is built, tested and accepted the same way.

How an engagement runs, from first conversation to lifecycle Seven stages from left to right: engage (estate goals), requirements (FR and NFR), discovery (estate today), design (reference), build and test (first pod), support (operations), lifecycle (evergreen). For each stage the panel shows who I work with and what comes out of it. After the lifecycle stage the loop returns to the start. Engageestate goals RequirementsFR and NFR Discoveryestate today Designreference Buildfirst pod Supportoperations Lifecycleevergreen Step 1 · EngageWhat the estate must do, and for how longWho I work withWhat comes outCIO, CTO and financeEnterprise architectsRisk and resilience leadsScope, drivers and constraintsService tiers and tolerancesBuild, colocate or cloud mixDecision log and owners Step 2 · RequirementsTiers, capacity and controls as numbersWho I work withWhat comes outDomain architectsSecurity and complianceOperations leadsRequirements by domainRecovery targets per tierCapacity forecast by familyRegulatory controls mapped Step 3 · DiscoveryWhat exists, who owns it, what it costsWho I work withWhat comes outData centre managersPlatform and network teamsProcurement and suppliersAsset and service inventoryHall power and cooling headroomShared service dependenciesContracts and end of life dates Step 4 · DesignFoundations first, then each domainWho I work withWhat comes outDesign authorityDomain architectsVendor architectsFoundations: terms, rules, tiersPod families and blocksDomain designs and interfacesAcceptance checklists Step 5 · Build and testFactory build, then one acceptance gateWho I work withWhat comes outIntegrators and makersFacilities and site teamsTest and operations teamsFactory test reportsSite readiness checklistAs built recordAcceptance report Step 6 · SupportRun as products, watched as one estateWho I work withWhat comes outOperations centresDomain product ownersService ownersObjectives and error budgetsRunbooks for every alertGame day calendarMonthly showback Step 7 · LifecycleRefresh, reuse and retire by designWho I work withWhat comes outDesign authorityFinance and procurementSustainability leadsGeneration plans by familyOrder windows and buffersRetirement certificatesUpdated standards

Swipe sideways to see the whole diagram.

Step 1
  1. I start with the estate, not a pod: which services it carries, how critical each one is, how fast demand grows and which rules apply. That sets the tiers, the size of the halls and how much to build, colocate or rent.

  2. Functional requirements say what each domain must provide. Non functional ones put numbers on recovery time and data loss for each tier, capacity, power, change safety and evidence. Every requirement traces to a decision and a test.

  3. I map what exists today: servers, platforms, services and their owners, the power and cooling left in each hall, hidden shared services, and the contracts and end of life dates that will shape the timetable.

  4. I write the foundations once: terms, principles, the pod model, tiers and failure domains. Each domain design then builds on them, and an overarching design checks that the domains fit, with every interface written as a contract.

  5. The first pod of each family is built in the factory, burned in, delivered whole and accepted against every domain's checklist. What we learn goes back into the family design before the second pod is ordered.

  6. Each domain team runs its platform as a product with its own on call. The operations centre watches the whole estate, error budgets gate risky change, and failovers and game days run on a calendar.

  7. Every pod has an end date from the day it is requested. Generation plans, order windows and two qualified makers keep refresh routine, and retired kit is wiped on site, reused where possible, then recycled.

Functional requirements

What it must do.

  • Build every pod from a catalogue family, to its fixed design.
  • Place every service by its tier, in every layer.
  • Keep each site running if the other site's shared services fail.
  • Give each region an isolated vault and clean room that can rebuild critical services.
  • Change every pod through pipelines, in waves.
  • Hold one record of every asset, pod, service and interface, each with an owner.

Non functional requirements

How well it must do it, with a number wherever one can be agreed.

Recovery
Most critical tier back within 15 minutes with no data lost, proved by test (typical).
Lead time
A standard pod from request to live in a few months when parts are in supply (typical).
Change safety
No change reaches every pod at once, and a spent error budget pauses risky change.
Capacity
Fitted power at least one block ahead of committed demand in every hall.
Efficiency
A design power usage effectiveness (PUE) target agreed for each hall and reported every year.
Evidence
Every gate, test and restore leaves evidence in the record.

Typical starting targets. Each organisation sets its own from its services and its regulators.

Projects

Related work behind this page

This page draws on my own reference architecture and on the data centre, resilience and design authority work closest to it.

Independent work · 2026

A reference architecture for hyperscale pods

I wrote a vendor neutral reference architecture for hyperscale pods: foundations, nine domain designs and an overarching design. This page shows its ideas and patterns; the designs themselves are not published.

XIDA · 2025 to now

AI ready data centre infrastructure Related

Designed infrastructure for high density compute clusters, covering network, power, cooling and structured cabling, with the rack layouts and deployment documentation the build teams worked from.

XIDA · 2021 to 2024

Lead architect from discovery to handover Related

Lead architect on network, cloud and data centre modernisation programmes from discovery to operational handover across several client environments, including Weetabix, Dyson, Virgin Media O2 and Network Rail.

Network Rail, with 2e2 · 2011 to 2013

A £25 million data centre from an empty shell Related

Led 3 engineers across 2e2 projects, including this build, which covered structured cabling, building management systems and mechanical and electrical integration, with building management and power monitoring on a segregated operational technology (OT) network.

AVEVA · 2020 to 2021

Data centre transitions at 99.99 percent Related

Safeguarded over £200 million of transactional services through data centre transitions, holding 99.99 percent uptime throughout.

Manx Telecom · 2016

A Tier 3 data centre Related

Tier 3 data centre and managed infrastructure for over 300 customer sites, on Cisco ACI and Nexus. The fabric side is on the data centre networks page.

Backed by PRINCE2 Practitioner, ITIL and TM Forum Architecture, and by focused training on data centre power, cooling and AI fabrics. See all credentials

This page explains a generic reference architecture to show how I design. It is not advice for any particular organisation or estate: every typical or indicative figure must be checked against the real requirement, and vendor and regulatory facts against their sources on the day. Product and standard names are trademarks of their owners.

Sources

Standards and sources behind this page

These are the primary references I check this page against. I last reviewed them on 28 November 2026. Where a figure is indicative, the page says so.

  1. NIST SP 800-207: Zero Trust Architecture, NIST. Trust based on identity rather than network location.
  2. Redfish, DMTF. The standard interface for managing servers over the out of band network.
  3. OpenTelemetry documentation, OpenTelemetry. One open standard for metrics, logs and traces from every layer.
  4. Certified Kubernetes Software Conformance, CNCF. The programme that certifies a Kubernetes distribution as conformant.
  5. Site Reliability Engineering: Embracing Risk, Google. Service level objectives and error budgets that set the pace of change.
  6. FIPS 203: Module Lattice Based Key Encapsulation Mechanism Standard, NIST. The first post quantum key exchange standard.
  7. NIST SP 800-88 Rev. 2: Guidelines for Media Sanitization, NIST. How to wipe or destroy data before kit is reused or recycled.
  8. SS1/21 Operational resilience: Impact tolerances for important business services, Bank of England. UK rules that tie recovery targets to important business services.
  9. Regulation (EU) 2022/2554, the Digital Operational Resilience Act, European Union. EU rules on incident reporting, resilience testing and third party risk.
  10. Tier Classification System, Uptime Institute. Data centre tiers, including concurrent maintainability.